LEVIATHAN SYSTEMS

Liquid Cooling_

Facility Water Loop Design for AI Halls: TCS to FWS Done Right

·Technical content·

Assess the facility-water interface to a liquid-to-liquid CDU: heat duty, circuit temperatures and hydraulics, compatible fluids, maintainable layouts and applicable readiness evidence.

Key facts

  • In an isolated liquid-to-liquid CDU arrangement, heat crosses the exchanger while FWS and TCS fluids remain separate. [A1]
  • Define the liquid heat duty and each circuit's fluid, flow and temperature points before comparing equipment requirements with a CDU rating.
  • Approach temperature and a circuit's return-minus-supply temperature rise describe different temperature differences. [O1]
  • Identify the pump and its circuit before interpreting pressure or elevation information.
  • Material compatibility depends on the actual fluid formulation and conditions; glycol alone does not establish copper incompatibility. [D1]
  • A test record needs the tested assembly boundary, including whether the CDU was included.
  • Liquid-cooling tie-ins, verification and commissioning are outside Leviathan's service scope.

Setting FWS Supply Temperature and Flow to Match CDU Performance

The arrangement considered here uses a liquid-to-liquid CDU between the facility water system (FWS) and technology cooling system (TCS). ASHRAE also describes non-CDU arrangements, so establish the actual architecture first. [A1] The buyer's task is to connect an identified IT liquid-cooling requirement to an applicable facility interface, with the customer's appointed qualified cooling, facility and OEM parties owning the design and work methods.

Establish the heat duty assigned to liquid at the selected equipment boundary. Rack electrical input or processor thermal design power cannot automatically supply that duty. The IT equipment's applicable temperature limits and heat-load basis are inputs to the comparison; the CDU manufacturer's performance information describes the exchanger under stated conditions.

For steady single-phase heat transport, heat duty equals volumetric flow × density × specific heat capacity × circuit temperature rise. TCS supply travels toward the IT; FWS supply travels toward the CDU. Evaluate each return-minus-supply rise using that circuit's fluid properties. The required flows can differ. [R1]

OCP defines approach temperature difference as TCS supply temperature minus FWS supply temperature. Its performance discussion treats both circuits' flow and temperature as rating conditions. [O1] In a fictional example, FWS supply is 25°C, TCS supply is 32°C and TCS return is 40°C. Approach is 32 − 25 = 7°C; TCS rise is 40 − 32 = 8°C. The FWS return is unspecified, so its rise is unknown. These invented temperatures explain the distinction; they select no setpoint, flow or CDU capacity.

Temperature selection also needs a local dew-point assessment: exposed surfaces below that dew point can collect condensation. The selected thermal design must address the relevant surfaces and operating conditions, including any insulation and controls. A warm-water label alone cannot settle that question. [O1]

Water Chemistry and Filtration Requirements for the Facility Loop

ASHRAE distinguishes FWS and TCS quality requirements and describes site-specific treatment. [A1] The useful design return identifies each circuit's fluid, wetted materials, applicable equipment limits and treatment owner. Copying a TCS specification into the facility-water package obscures the interface it is intended to protect.

Side-stream filtration processes part of the flow over time; endpoint filtration protects the CDU interface from arriving particles. ASHRAE discusses both. [A1] Ask the CDU supplier and facility designer to identify the protection provided by the proposed arrangement and its maintenance access.

A water-quality record becomes useful when it names the circuit, sampling location, fluid and applicable limits. The appointed treatment and equipment parties determine the relevant parameters, sampling methods and intervals. A conductivity or turbidity number detached from those details cannot establish compatibility. Treatment equipment, inhibitor or biocide requirements and BMS signals belong to that actual design; there is no universal skid, residual or sensor package in this article.

Locating and Configuring Tie-In Points for CDU Arrays

Maintainable isolation remains a useful objective. Ask the designer to show the intended service boundary on the actual piping and instrumentation diagram (P&ID): which CDU or branch is affected, what remains connected and what access is needed for the selected maintenance task. A drawing that labels a unit isolatable should also make its facility and technology connections distinguishable. Valve and drain geometry follow the selected equipment and site design.

Hydraulic information also needs its circuit attached. OCP treats TCS pumping head and FWS flow impedance separately. [O1] Vertiv's XDU450 guide identifies secondary pumps and a plate exchanger separating the primary and secondary circuits. [V1] The resulting circuit-boundary inference is straightforward: primary tie-in height cannot establish those isolated secondary pumps' suction conditions. Identify the actual pump, fluid circuit and applicable assessment.

For an array, obtain the designer's applicable branch-flow and pressure basis and the selected CDU's corresponding requirements. A header pressure observation alone leaves individual branch conditions unresolved. The responsible parties must define balancing methods for the actual network; neither a header-outward nor a farthest-branch-inward order is established here. Keep equipment and circuit tags consistent with the current drawings so later observations refer to the intended interface.

Piping Material, Support, and Routing in GPU Halls

Compatibility concerns the actual fluid formulation, concentration, materials and operating conditions. Dow describes DOWFROST LC 25 as an inhibited propylene-glycol TCS fluid for direct-to-chip applications with high-surface-area copper components. [D1] This named counterexample defeats a blanket copper/glycol ban. It supplies no approval for a particular facility loop, mixed-material assembly or substitute fluid; obtain the applicable equipment and fluid suppliers' compatibility requirements.

OCP's liquid-distribution guidance discusses thermal movement, vibration and building movement, with flexible connectors and grooved couplings among the design considerations. It also identifies space for component replacement and drainage. [R1] A vertical riser or raised-floor route does not alone determine that an expansion loop is the required solution.

Ask the appointed designers to resolve the filled-pipe support design, movement provisions, insulation, service access and adjacent electrical and IT routes in the released layout. Preserve installation and replacement access when comparing revisions. A GPU family name supplies no clearance dimensions.

Interpreting Problems at the FWS-to-CDU Interface

A change in cooling performance is an observation to locate before it becomes a diagnosis. Identify whether the recorded temperature, flow or pressure belongs to the FWS branch, CDU or TCS distribution, and retain the configuration and operating conditions. A note saying CDU trip without the corresponding event and circuit information cannot distinguish a facility-interface problem from a technology-side issue.

For example, a hypothetical report might say rack return temperature increased while header pressure remained stable. That report leaves the affected branch flow, TCS conditions and heat duty unspecified. It therefore cannot establish fouling, trapped air, cavitation or a defective cold plate as the cause. The useful follow-up is the applicable equipment information and responsible specialist's assessment of the observations, rather than an improvised fill, flush or valve intervention.

Compare evidence taken at equivalent boundaries and conditions. A trend following a configuration or fluid change needs that change recorded; otherwise a numerical comparison may conceal a different question. An alarm-free interval documents that interval. It supplies no automatic conclusion about performance at another load or about every branch on a shared header.

Readiness Evidence and Authorized Load Validation

Separate readiness for the proposed next activity from demonstrated performance under load. Pre-load readiness evidence can document completed prerequisites and unresolved items within its stated scope. Authorized load validation later records performance at its actual conditions. If the first GPU power-on supplies the load, its result cannot already be evidence available before that same event. Any alternative load-validation arrangement must be identified in the responsible parties' plan.

The tested assembly boundary matters as much as the report title. Vertiv's XDU450 guide, section 6.1.1, distinguishes leak checking field-installed piping from testing with the unit included. [V1] Ask the cooling owner which assembly the returned record covers, which equipment was included or excluded, and which applicable OEM and site requirements governed it. Product qualification and installed-system evidence serve different scopes. No generic pressure, duration, decay limit or flushing endpoint is supplied here.

A useful return connects the actual configuration and boundary to the activity, criteria, conditions, observations, exceptions and responsible disposition. The customer's appointed parties determine whether that evidence supports the next authorized activity. Physical installation records retain their own scope.

Leviathan does not perform, coordinate or subcontract liquid-side work. Its separately agreed physical IT work can include equipment installation, IT cabling, labels and handoff records; hardware QA requires engagement-defined methods, resources and acceptance criteria. For a rack-and-stack discussion, use the project inquiry below with the equipment list, released rack and cable documents, requested physical tasks and customer-defined cooling prerequisites. The related cooling-responsibility page explains the specialist boundary. Scope, site requirements and availability determine the engagement.

Standards referenced: A1 — ASHRAE TC 9.9, Water-Cooled Servers: Common Designs, Components, and Processes (2019; October 10, 2019 errata incorporated), printed pp. 8–12, 19–21, 25–29. Architecture, chemistry and filtration concepts. https://www.ashrae.org/File%20Library/Technical%20Resources/Bookstore/WhitePaper_TC099-WaterCooledServers.pdf · O1 — OCP, Liquid to Liquid CDU Test Methodology and Performance Rating, Revision 1.0. Headers: August 2024; version table: 11/01/2024. Sections 3.3.2.1–3.3.2.3: approach temperature, TCS head and FWS impedance. CDU qualification context, without a field-test prescription. https://www.opencompute.org/documents/ocp-wp-l-lcdu-test-methodology-performance-rating-r1-pdf · R1 — OCP, Data Center Liquid Distribution Guidance & Reference Designs, Revision 1.0, January 8, 2024, printed pp. 7–9. Conceptual heat transport, routing, movement and condensation considerations. https://www.opencompute.org/documents/ocp-acf-reference-design-guidance-white-paper-r1-pdf · V1 — Vertiv, Liebert XDU450 Installation and Commissioning Guide, publicly hosted edition marked ©2022, sections 3.1, 3.3 and 6.1.1. Named circuit architecture and tested-boundary example; its operating and test values are not generalized. https://www.vertiv.cn/4a1b3b/globalassets/products/thermal-management/high-density-solutions/liebert-xdu450-coolant-distribution-unit-installation-and-commissioning-guide-sl-70624.pdf · D1 — Dow, DOWFROST LC 25 Heat Transfer Fluid, public product description checked October 20, 2026; publication date not established. Named copper-compatible TCS formulation, without project compatibility approval. https://www.dow.com/en-us/pdp.dowfrost-lc-25-heat-transfer-fluid.497419z.html

Frequently asked_

How is FWS flow balanced to multiple CDUs on the same header?

The applicable network design and selected CDU requirements establish the branch targets and balancing method. Keep FWS conditions separate from TCS pumping conditions. The evidence should identify the assessed branches and operating configuration; this article establishes no balancing order or secondary-isolation procedure.

What water quality parameters must be checked at the CDU inlet?

Use the identified circuit's applicable equipment and treatment requirements. Record the fluid, sample location, relevant parameters and limits together. FWS and TCS requirements must remain distinguishable; a generic list of conductivity, pH and turbidity is not a complete treatment specification.

Where should isolation valves be placed relative to the CDU?

The selected CDU requirements and site design determine the arrangement. Ask the released drawing to identify the intended service boundary, affected connections and maintenance access. A generic valve-location statement cannot establish that an entire unit can be removed while neighboring circuits remain available.

What test confirms the FWS loop is ready for CDU connection?

Readiness depends on the proposed activity and applicable requirements. Identify the tested assembly, included equipment, method, criteria, conditions, results and responsible disposition. A piping test alone leaves chemistry, thermal performance and other prerequisites unresolved; it does not establish one universal ready-for-connection conclusion.

Who typically performs the final FWS-to-CDU tie-in verification?

Cooling-system verification and acceptance are outside Leviathan's physical IT scope; identify the customer-nominated qualified cooling, facility and OEM parties responsible for that work.

Discuss Your Infrastructure Project_

Tell us about your project, and our team will follow up to discuss the scope, requirements and availability.

Discuss a ProjectEmail Project Scope