Liquid Cooling
Warm-Water Cooling for GPU Clusters: Why Hotter Water Wins
Assess warm-water GPU cooling benefits against equipment flow limits, local climate, condensation conditions and a realistic heat-reuse opportunity.
Key facts
- Warmer supported coolant can expand economizer cooling opportunities; the highest permitted inlet temperature is not automatically the best system operating point. [W1, W3]
- ASHRAE's fifth-edition reference card uses W32 and W45 for classes with maximum facility-water supply temperatures of 32°C and 45°C. [W2]
- A liquid-to-liquid CDU separates facility water from the technology cooling circuit; their supply temperatures are different quantities. [W4]
- Lenovo's Type 7DJV table links warmer supply to higher required flow and rack pressure drop. [W3]
- Heat reuse depends on the receiving load's temperature, location and availability as well as the heat leaving the data center. [W5]
- Condensation depends on an exposed surface's temperature relative to the dew point of the air touching it. A warm-water label does not settle that comparison. [W6]
- NVIDIA's named DGX GB rack uses a passive copper NVLink backplane and liquid manifolds; the backplane's medium does not establish hose-routing rules. [W7]
01
Raising Supply-Water Temperature for Economizer Cooling
Hotter water wins when the selected equipment supports it and the facility gains more from the warmer operating point than it incurs elsewhere. The opportunity is reduced mechanical refrigeration and potentially more useful recovered heat. The buyer's decision is whether that benefit survives the actual equipment and site constraints, rather than whether a temperature is simply higher.
A warmer supported cooling-water temperature can make outdoor heat rejection possible for more hours. Dry coolers depend on outdoor dry-bulb temperature; evaporative heat rejection depends on wet-bulb conditions and consumes water. Economizer operation still uses equipment such as fans and pumps, so free cooling does not mean zero cooling energy. ASHRAE's 2023 Handbook also requires accounting for the planned CDU's approach temperature at the IT interface. One rack-inlet reading compared with outdoor wet bulb cannot establish the whole heat-transfer path. [W1]
The fifth-edition ASHRAE reference card, copyright 2021/2024, identifies W32 and W45 with maximum facility-water supply temperatures of 32°C and 45°C. These are class boundaries, not recommended CDU setpoints. Its descriptions retain location-dependent limits on chiller-free operation and dry-cooler suitability. An equipment class alone supplies no annual savings figure. [W2]
02
Capturing Waste Heat for Facility Reuse
OCP's Data Centers Heat Reuse 101 makes reuse conditional on a suitable nearby consumer and useful temperature. Consistent demand differs from seasonal demand; warm return water alone does not guarantee a heating service. [W5]
Direct exchange must suit the receiving temperature. A heat pump may be needed where it does not; include its energy and cost, the thermal network and connection distance. [W5]
In a fictional winter-only building, summer operation still needs heat rejection. Ask how the proposal handles that mismatch before crediting annual reuse.
03
Condensation Depends on Surfaces and the Cooling Circuit
In ASHRAE's liquid-to-liquid CDU arrangement, the facility water system (FWS) and technology cooling system (TCS) are separate circuits. FWS can be colder than hall dew point; its temperature cannot stand in for rack coolant temperature. [W4]
Vaisala's cold-pipe explanation locates condensation at the exposed surface and the air surrounding it. Warmer coolant may help keep a relevant surface above local dew point, but bulk supply temperature alone does not establish every surface's condition. It also cannot justify removing insulation throughout a row. [W6]
The useful proposal identifies which circuit and exposed surfaces its condensation claim covers, and the environmental conditions on which that claim depends. A statement about normal operation leaves cold startup conditions or humidity excursions unanswered unless its supporting assessment covers them. The related condensation guide develops that separate decision.
04
Read the Actual Rack Arrangement Before Planning IT Access
NVIDIA's DGX GB guide describes the passive copper NVLink backplane separately from the liquid manifolds and rear service access. This identifies components, not universal hose-routing rules. [W7]
Its compute trays use CPU/GPU cold plates and retain air-cooled components, so liquid cooling does not eliminate the hall's air-cooling duty. [W7]
Plan physical IT access from the supplied rack documents and released constraints. A communication medium cannot establish hose positions, fittings or clearances.
05
Read Temperature, Flow and Pressure Drop Together
ASHRAE's 2019 white paper defines the TCS upper temperature bound at a given flow. That boundary is not permission to exceed the applicable equipment envelope. [W4]
Lenovo's model-qualified GB300 NVL72 Type 7DJV table pairs 25°C supply with 59 LPM and 2.3 psi rack pressure drop; 45°C requires 177 LPM and 18.4 psi. [W3]
Those points mean three times the flow and eight times the pressure drop. Include hydraulic demand in the energy comparison; neither ratio measures pump energy. Pressure drop is not allowable static pressure.
A fictional offer combining 45°C and 59 LPM mixes rows. Request consistent requirements before crediting its promised savings.
06
Turn the Warm-Water Claim into a Complete Buyer Comparison
Ask the cooling proposal to connect the exact equipment envelope to the facility's annual cooling assessment: which circuit runs warmer, which climate and rejection mode were assessed, what auxiliary energy is included, and whether a real heat consumer is available. A compressor-energy reduction alone does not establish the complete system benefit. Keep any claimed saving attached to its stated configuration and assumptions.
Warm water also leaves the cold plate's other requirements in place. ASHRAE's September 2025 public cold-plate excerpt identifies temperature, flow, pressure drop, material compatibility and cleanliness as equipment-specific requirements. Its description of fluid channels explains why an inlet-temperature label cannot establish the condition or heat-transfer performance of the complete cooling path. [W8]
The appointed qualified OEM, cooling and facility parties own the actual design, applicable code requirements, operating conditions, procedures and cooling acceptance. Leviathan delivers the physical IT installation, IT cabling and documentation.
Use the related Liquid Cooling Responsibilities & IT Installation guide to define that boundary. For an IT project discussion, provide the equipment list, released rack and cable documents, work-window constraints and readiness information supplied by the responsible cooling parties. The linked project inquiry is for discussing that physical IT scope, requirements and availability.
07FAQ
Frequently asked
What water temperature should the CDU be set to for a new GB300 NVL72 row?
Does warm-water cooling guarantee condensation-free manifolds?
Does NVLink's copper backplane determine cooling-hose routing?
Does a rise in GPU temperature prove that the water is too warm?
Who performs the final leak test before a warm-water row is released to production?
08Related
Related
Cooling responsibilities and physical IT installation scope
Discuss physical IT work around a supplied cooling system
Condensation: exposed surfaces and dew-point conditions
CDU capacity: rating conditions and equipment requirements
W1: ASHRAE 2023 Handbook — cooling interfaces and economizers
W2: ASHRAE fifth-edition reference card — liquid-cooling classes
W3: Lenovo Type 7DJV — temperature, flow and rack pressure drop
W4: ASHRAE Water-Cooled Servers — circuits and temperature bounds
W5: OCP Data Centers Heat Reuse 101 — heat-host applicability
W6: Vaisala — dew point and surface condensation
W7: NVIDIA DGX GB hardware — rack components and cooling coverage
W8: ASHRAE Journal — cold-plate requirements
Closed-Loop Cooling Can Still Use Water: Read the Facility Boundary
Contact
Discuss Your Infrastructure Project
Tell us about your project, and our team will follow up to discuss the scope, requirements and availability.